DESCRIPTION | |
AE transducers convert various electrical power line parameters viz. Voltage, Current, Frequency, Power Factor, Active power, Reactive power, Apparent power into load independent DC current or voltage output. These are used in various electrical, thermal, chemical & other power plants to monitor processed data either locally or remotely, using various devices such as indicating meters, data loggers, recorders, SCADA systems. |
FEATURES | |
• | Open & short circuit protected. |
• | Current and Voltage output are indendent of load impedance. |
• | Measurement of DC parameters. |
ELECTRICAL SPECIFICATIONS | ||||||||
• | TYPE | Ohm, DC / AC Voltage, DC / AC Current, Frequency, Summation, Power Factor, DC / AC Watt, Var, VA Transducers. | ||||||
• | INPUT RANGE | |||||||
VOLTAGE | 0 - 500V DC / 0 - 500V AC. | |||||||
CURRENT | 0 - 5A DC (for higher ranges 50 - 300mV ext. Shunt) / 0 - 5A AC. | |||||||
FREQUENCY | 50 / 60Hz ± 5hz., 400hz ± 20Hz. (other Frequency on request). | |||||||
POWER FACTOR | 0.5% (lag) - unity - 0.5(lead). (Refer Note 4) | |||||||
RESISTANCE | 0 - 500Ω for Ohm Transducer | |||||||
• | ACCURACY | 0.5% of f.s.d. for Ohm, Voltage, Current, Summation, Power Factor, Watt, Var, VA Transducers. For Frequency Transducer - 0.2% of Centre frequency. |
||||||
• | AUX. SUPPLY | 63.5V, 110V, 220V, 230V, 240V, 380V, 415V, 440V AC ±10%, 50/60Hz. 24V, 48V, 110V, 220V DC ±10% |
||||||
• | VA BURDEN | For VOLTAGE ≤ 1.0, For CURRENT ≤ 0.5, for AUX Supply ≤ 4.0 | ||||||
• | OUTPUT RANGE | |||||||
CURRENT MAX. LOAD |
0 - 1mA | 0- 5mA | 0 - 10mA | 0 - 20mA | 4 - 20mA | 10 - 0 - 10mA. | ||
10kΩ | 2kΩ | 1kΩ | 500Ω | 500Ω | 1kΩ | |||
VOLTAGE MIN. LOAD |
0 - 1V | 0 - 5V | 0 - 10V | 1 - 5V | 2 - 10V | 10 - 0 10V | ||
500Ω | 2.5Ω | 5kΩ | 2.5kΩ | 5kΩ | 5kΩ | |||
• | RIPPLE | Maximum 0.5% of span. | ||||||
• | OVERLOAD CAPACITY | |||||||
• VOLTAGE continuous | 120% of nominal | |||||||
short term(10sec) | 150% of nominal | |||||||
• CURRENT continuous | 120% of nominal | |||||||
short term(3 sec) | 10 times of nominal | |||||||
• | RESPONSE TIME | 300 msec. | ||||||
• | OPEN CKT. VOLTAGE | 22 Vmax. | ||||||
• | IMPULSE VOLTAGE | Peak Voltage of 5kV, Standardized impulsed waveform of 1.2 / 50µsec. | ||||||
• | INSULNRESISTANCE | Greater than 20 Mohms at 500V DC | ||||||
• | DIELECTRIC TEST | 2kV RMS for 1 minute (4kV on request) | ||||||
• | OPERATING TEMP. | 0°C to 55°C | ||||||
• | STORAGE TEMP. | -20°C to 70°C | ||||||
• | HUMIDITY | Upto 95% RH | ||||||
• | CONFORMS TO | I.S.12784 (Part 1)/ I.E.C. 688 |
MECHANICAL SPECIFICATION | Transducers Panel Cum Din Rail Mounting | ||
Mounting Rail EN 50022 |
|||
2 mounting holes φ4.5mm for M4, 40 ~ 50 mm OR Equivalent screw | M3 x 15 mm screw 4 terminals in 2 rows Lug width 6.0 ~ 6.4 mm | 4 mounting holes Ø 5mm For M4, 20 ~ 25mm OR Equivalent screw |
M3 X 10mm screw 8 Terminals in 2 Rows |
MODEL | PD1 | PD2 | PD3* |
HEIGHT | H = 123 mm | H = 80mm | H = 115 mm |
AUX. SUPPLY | AC / DC Auxiliary | AC Auxiliary* | DC Auxiliary |
Type | Ohm Transducer | Summation Transducer | |
DC Voltage Transducer | Single Phase Power Factor Transducer | ||
DC Current Transducer | 3 Phase Single Element Power Factor Transducer | ||
Frequency Transducer | Unipolar output | Bipolar output* | |
AC Voltage Transducer | 3 Phase 2 Element Watt / Var / VA Transducer* | ||
AC Current Transducer | 3 Phase 3 Element Watt / Var / VA Transducer* |
*TYPE | 3 Phase 2 Elemet & 3 Phase 3 Element Watt or Var Transducers with AC Auxiliary supply and Bipolar output are available in MODEL PD3. |
Note : | |
1) | Self - Powered AC Voltage, Current, Frequency , PF & Power Transducers are available on request. |
Self - Powered Voltage & Current transducers operate for input variation between 10% to 120% of the range. | |
Self - Powered Frequency, Power and Power Factor Transducers operate on ±10% of rated voltage. | |
2) | The individual output, in dual output transducers, are not isolated from each other. |
3) | Summation Transducers Maximum Inputs - 5 nos.; No isolation between any two inputs & between input & output. |
4) | Output of power factor transducers is proportional to phase angle. |
Ordering information | ||||
1)Type 2) Model 3) Input Range 4 a) Output Range (Current / Voltage ) 4 b) Single or dual 5) Aux. Supply |
ADDITIONAL INFORMATION | ||
• | Power & Power Factor | 1) Voltage (PTR) 2)Frequency 3) Current (CTR) |
• | Summation | 1) No. of inputs |
* To embrace new technologies and methods. * To give unsurpassed products and services to the clients. * To constantly look for improvement and changes.